Line 1: Line 1:
-====== Devices wiring ======+====== LCS Devices wiring ======
  
  
Line 8: Line 8:
 Individual lights (or hard-wired light groups) are wired directly to the distribution box with an appropriate wire gauge (usually 3 × 1,5 mm<sup>2</sup>). Individual lights (or hard-wired light groups) are wired directly to the distribution box with an appropriate wire gauge (usually 3 × 1,5 mm<sup>2</sup>).
  
-Push-button flush boxes are wired directly to the distribution box with signal wires. One wire for each push-button and one common wire (for 3 push-buttons: 4 × 0,5 mm<sup>2</sup>). Push buttons that are controlling same light are connected to the same input in parallel.+===== Push-button flush boxes are wired: ===== 
 +directly to the distribution box with signal wires. One wire for each push-button and one common wire (for 3 push-buttons: 4 × 0,5 mm<sup>2</sup>). Push buttons that are controlling same light are connected to the same input in parallel
  
-Sensors are wired directly to distribution box. More sensors can be used for same light. Presence sensors must be wired in **parallel**read sensors in **series**.+directly to the distribution box with Cat5+ cableUp to four buttons on one Cat5+ cable. One core wire for each push-button and one twisted pair for common (for 4 push-buttons: Cat 5+<sup>2</sup>). Push buttons that are controlling same light are connected to the same input in parallel. 
 + 
 +===== Motion sensors are wired: ===== 
 +- directly to the distribution box with signal wires. One wire for each sensor and one common wire (for 3 push-buttons: 4 × 0,5 mm<sup>2</sup>). Sensors that are controlling same light are connected to the same input in parallel
 + 
 +- directly to the distribution box with Cat5+ cable. Up to four sensors on one Cat5+ cable. One core wire for each sensorone twisted pair for +24 VDC power supply and one twisted pair for 0 VDC (ground) power supply  (for 4 sensors: Cat 5+<sup>2</sup>). Sensors that are controlling same light are connected to the same input in parallel. 
 +More sensors can be used for the same light.
  
 |< 60% 15% 85% >| |< 60% 15% 85% >|
Line 35: Line 42:
 |< 60% 15% 85% >| |< 60% 15% 85% >|
 ^ DALI Light                  | {{hiq_building_automation:hiq_home:methods:wiring:dali_light_wiring.png?nolink|}}       | ^ DALI Light                  | {{hiq_building_automation:hiq_home:methods:wiring:dali_light_wiring.png?nolink|}}       |
- 
-<WRAP pagebreak></WRAP> 
- 
-===== Individually managed sockets ===== 
- 
-{{hiq_building_automation:hiq_home:methods:wiring:individual_sockets.png?nolink&1000|}} 
- 
-Individual sockets are wired directly to the distribution box with an appropriate wire gauge (usually 3 × 2,5 mm<sup>2</sup>) 
- 
-Push-button flush boxes are wired directly to the distribution box with signal wires. One wire for each push-button and one common wire (for 3 push-buttons: 4 × 0,5 mm<sup>2</sup>) 
- 
- 
-|< 60% 15% 85% >| 
-^ Managed sockets                  | {{hiq_building_automation:hiq_home:methods:wiring:socket_wiring.png?|}}       | 
- 
-<WRAP pagebreak></WRAP> 
- 
-===== Group managed sockets ===== 
- 
-{{hiq_building_automation:hiq_home:methods:wiring:group_sockets.png?nolink&1000|}} 
- 
-Sockets group is wired to the distribution box with an appropriate wire gauge (usually 3 × 2,5 mm<sup>2</sup>) 
- 
-Push-button flush boxes are wired directly to the distribution box with signal wires. One wire for each push-button and one common wire (for 3 push-buttons: 4 × 0,5 mm<sup>2</sup>) 
- 
- 
-<WRAP pagebreak></WRAP> 
- 
-===== Blinds motors ===== 
- 
-{{hiq_building_automation:hiq_home:methods:wiring:blinds.png?nolink&1000|}} 
- 
-Blind motors are wired directly to the distribution box with an appropriate wire gauge (usually 4 × 1,5 mm<sup>2</sup>) 
- 
-Push-button flush boxes are wired directly to the distribution box with signal wires. One wire for each push-button and one common wire (for 2 push-buttons (up/down): 3 × 0,5 mm<sup>2</sup>) 
- 
-|< 60% 15% 85% >| 
-^ Blinds motor        | {{hiq_building_automation:hiq_home:methods:wiring:blinds_wiring.png?nolink|}}          | 
-^ Blinds push-buttons | {{hiq_building_automation:hiq_home:methods:wiring:blinds_pb_wiring.png?nolink|}}       | 
- 
-<WRAP pagebreak></WRAP> 
- 
-===== Exhaust fan ===== 
- 
-{{hiq_building_automation:hiq_home:methods:wiring:fans.png?nolink&1000|}} 
- 
-Exhaust fans are wired directly to the distribution box with an appropriate wire gauge (usually 3 × 1,5 mm<sup>2</sup>) 
- 
-Push-button flush boxes are wired directly to the distribution box with signal wires. One wire for each push-button and one common wire (for 1 push-button: 2 × 0,5 mm<sup>2</sup>) 
- 
-|< 60% 15% 85% >| 
-^ Exhaust fan motor        | {{hiq_building_automation:hiq_home:methods:wiring:fans_wiring.png?nolink|}}          | 
- 
-<WRAP pagebreak></WRAP> 
- 
-===== HVAC ===== 
- 
-{{hiq_building_automation:hiq_home:methods:wiring:hvac_wiring.png?nolink&1000|}} 
- 
- 
-Radiator valves and boiler enable signal are wired directly to the distribution box with an appropriate wire gauge (usually 3 × 1,5 mm<sup>2</sup>) 
- 
-Thermostat is field module - see [[en:hiq_home:methods:wiring#Field modules|Field modules wiring]]. 
- 
-|< 60% 15% 85% >| 
-^ Radiator valve  | {{hiq_building_automation:hiq_home:methods:wiring:radiator_wiring.png?nolink|}}     | 
  
 <WRAP pagebreak></WRAP> <WRAP pagebreak></WRAP>
Line 115: Line 56:
     * SC-4O-IQ     * SC-4O-IQ
     * SC-4S-IQ     * SC-4S-IQ
-  * HVAC controllers 
-    * TH-1M-IQ 
-    * TH-1T-IQ 
-    * TH-2-IQ 
-    * TH-3-IQ 
-  * HVAC actuators 
-    * FC-1-IQ 
  
 |< 60% 15% 85% >| |< 60% 15% 85% >|
Line 135: Line 69:
 ^ LED stripe    | {{hiq_building_automation:hiq_home:methods:wiring:led_rgb_wiring.png?nolink|!!    }}   | ^ LED stripe    | {{hiq_building_automation:hiq_home:methods:wiring:led_rgb_wiring.png?nolink|!!    }}   |
  
- 
-|< 60% 15% 85% >| 
-^ Fan-Coil Fan    | {{hiq_building_automation:hiq_home:methods:wiring:fc-fan_wiring.png?nolink|}}     | 
-^ Fan-Coil Valve  | {{hiq_building_automation:hiq_home:methods:wiring:fc-valve_wiring.png?nolink|}}     | 
  
  
en/ms_main/wiring.1589571824.txt.gz · Last modified: 2020/05/15 19:43 by marjan_strnad