====== myHIQ Home ====== **myHIQ** is a custom application built for specific projects based on CybroMiniScada. It can be fully customized for end-user needs. {{gallery> hiq_building_automation:hiq_home:sw:myhiq:examples?3 }} ---- {{hiq_building_automation:hiq_home:sw:myhiq:myhiq.zip|myHIQ demo app}} ===== CyBroMiniScada variables ===== {{hiq_building_automation:hiq_home:sw:myhiq:variables.png?nolink|}} |<50% 30% 20% >| ^ home controller address | c+//home controller address// | find on silver sticker on top of HC-HIQ | ===== On/Off devices ===== All On/Off devices (lights, managed power sockets, exhaust fans, ...) are controlled by LC-10-IQ device controller. myHIQ application displays device status and allows to toggle device output. **Device controller variables** |<50% 15% 15% 20% >| ^ HIQ-DC ^ id ^ output ^ description | ^ LC-10-IQ | lc00..lc04 | qx00..qx09 | r/w; 0=off, 1=on | ===== Dimmers ===== Dimmable dvices (lights and some ceiling fans) are controlled by several device controllers, depending on controlled devices: * LD-V4-IQ for LED stripes * LD-P4-IQ for 230 V dimmable lights and ceiling fans * LD-D8-IQ for DALI lights myHIQ application displays the device's on / off status and output intensity, and allows to control both. **Device controller variables** |<50% 15% 15% 20% >| ^ HIQ-DC ^ id ^ output ^ description | ^ LD-V4-IQ \\ LD-P4-IQ \\ LD-D8-IQ | ld00..ld04 | qx00..qx03 | r/w, 0=off, 1=on | ^ ::: | ::: | qw00..qw03 | r/w; 0..100 % | ===== Blinds ===== Blinds are controlled by a BC-5-IQ device controller.myHIQ application displays and sets the blind position. **Device controller variables** |<50% 15% 15% 20% >| ^ HIQ-DC ^ id ^ output ^ description | ^ BC-5-IQ | bc00..bc01 | qxs00up..qxs04up | r/o; 0=off, 1=moving up | ^ ::: | ::: | qxs00dn..qxs04dn | r/o; 0=off, 1=moving down | ^ ::: | ::: | blinds_position_00..04 | r/o; 0..100 % | ^ ::: | ::: | blinds_setpoint_00..04 | r/w; 0..100 % , -1=stop | ===== Scenes ===== Scenes are implemented directly in HIQ-HC. There is no need to use scene controller for using scenes from myHIQ application. **Home controller variables** |<50% 15% 15% 20% >| ^ HIQ-HC variable ^ id ^ description | | scene_status[0] | index=0..31 | r/o; 0=scene inactive, 1=scene active, 255=scene not defined | | global_scene_request | / | w/o; 0..31=set scene 0..31, -1=idle | | global_memory_request | / | w/o; 0..31=memorize scene 0..31, -1=idle | ===== Thermostats ===== Temperature regulation is done using TH-1M-IQ, TH-1T-IQ or TH-2-IQ thermostat and FC-1-IQ for fan-coils or HC-IQ for radiators. **Device controller variables** |<50% 15% 15% 20% >| ^ HIQ-HC ||^ description | ^ HC-IQ | hvac_mode || r/w; 0=off, 1=heating, 2=cooling | | |||| ^ HIQ-DC ^ id ^ output ^ description | ^ TH-1M-HIQ \\ TH-1T-IQ \\ TH-2-IQ | th00..th04 | setpoint | r/w; *0.1 °C (234=23.4 °C) | ^ ::: | ::: | temperature | r/o; *0.1 °C (234=23.4 °C) | ^ ::: | ::: | humidity | r/o; % RH | ^ ::: | ::: | active | r/w; 0=inactive (uses idle setpoint), 1=active (use setpoint) | ^ FC-1-IQ | fc00..fc04 | valve | r/o; 0=off, 1=on | ^ ::: | ::: | fan_speed | r/o; 0..3 |