en:hems_v1_2_0:commissioning

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
en:hems_v1_2_0:commissioning [2021/11/17 10:26] – [Digital output] gdzampoen:hems_v1_2_0:commissioning [2021/11/19 14:18] (current) – [Three-phase power-sensor] gdzampo
Line 70: Line 70:
   * After a few seconds, the sensor should appear as the "new device"   * After a few seconds, the sensor should appear as the "new device"
   * If desired, the sensor can be removed or it can be assigned to another device   * If desired, the sensor can be removed or it can be assigned to another device
 +<WRAP pagebreak></WRAP>
 ==== Power plant connection ==== ==== Power plant connection ====
  
Line 173: Line 173:
 ==== Digital output ==== ==== Digital output ====
  
-HEMS is supporting up to 8 digital outputs on MC controller (QX0,QX1,QX2,QX3,IO12,IO13,IO14 and IO15). Using HEMS configurator on settings page define Digital output for desired consumer (e.g. Digital-2). On IO MUX page assign digital to output port (e.g. IO15 -> Digital 2). So, in this case consumer 2 (Digital-2) is assigned to IO15 port and enables ON/OFF functionality. +HEMS is supporting up to 8 digital outputs on MC controller (QX0,QX1,QX2,QX3,IO12,IO13,IO14 and IO15). How to set?  
 +  * using [[en:hems_v1_2_0:software|HEMS configurator]] on settings pagedefine digital output for desired consumer (e.g. Digital-2),  
 +  * on IO MUX page assign digital to output port (e.g. IO15 -> Digital 2)in this case consumer 2 (Digital-2) is assigned to IO15 port and enables ON/OFF functionality on it.  
 + 
 +**Note**: if it is set **digital** for consumer without assigned power sensor, it is possible to define **P nominal** power instead. It represents fixed power of consumer and while in operating mode HEMS calculates consumed energy.  
 + 
 +==== Analog output ==== 
 + 
 +On port IO14 is supported analog output 0-10V, while on IO15 is PWM signal with frequency of 1kHz. Using analog load is possible for consumer 1 only! How to set ([[en:hems_v1_2_0:wiring|HEMS wiring]])?   
 +  * using [[en:hems_v1_2_0:software|HEMS configurator]] on settings page, define analog output for consumer 1,  
 +  * on IO MUX page define IO14 and/or IO15 port for Analog/PWM output, 
 +  * on home screen define analog value 0-100% (long-press) for consumer1 and turn it ON/OFF with short-press.  
 + 
 +**Note**: if it is set **analog** for consumer without assigned power sensor, it is possible to define **P nominal** power instead. It represents fixed power of consumer and while in operating mode HEMS calculates consumed energy.  
 + 
 +==== IO mux ==== 
 + 
 +IO mux page within [[en:hems_v1_2_0:software|HEMS configurator]] allows setting of input/output types for ports on controller:  
 +  * e.g. if it is set QX2 -> Router reset, it means that when conditions are met (for reset), QX2 port will change state to turn OFF router, 
 +  * or if it is set QX2 -> Digital-2, it means that digital2 (consumer 2) is assigned to QX2 and enables switching ON/OFF on it, 
 +  * for input ports IX0,IX1 and IX2 it is possible to set toggle and enable functionality ([[en:hems_v1_2_0:wiring|HEMS wiring]]). it means that dedicated consumer will be directly managed (ON/OFF) by input signal on IX0,IX1 or IX2. 
  
-Note: if it is set Digital for consumer without assigned power sensor, it is possible to define P nominal power instead. It represents fixed power of consumer and while in operating mode HEMS calculates consumed energy.  
  
 ==== Permanent memory ==== ==== Permanent memory ====
en/hems_v1_2_0/commissioning.1637144810.txt.gz · Last modified: 2021/11/17 10:26 by gdzampo