User Tools

Site Tools


en:hiq_hw:mc3-24

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
en:hiq_hw:mc3-24 [2019/08/14 13:08] – created goran.kocjancicen:hiq_hw:mc3-24 [2023/01/24 15:13] (current) – [Technical specification] saso_santelj
Line 1: Line 1:
 ====== Master Controller ====== ====== Master Controller ======
  
 +**Advanced Controller**
 +
 +<WRAP column 350px>
 +
 +{{ :en:hiq_hw:pasted:mc-24-c3.png?nolink |}}
 +
 +</WRAP>
 +
 +<WRAP column 600px>
 +
 +| Model number: ^ MC-24-05  | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals                         |
 +| :::           ^ MC-24-06  | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals, EnOcean                |
 +| Mounting:     | DIN rail(35mm), 6M, 106mm                                                                 ||
 +| Dimensions:   | 106x108x58mm                                                                        ||
 +
 +
 +</WRAP>
 +
 +<WRAP clear></WRAP>
 +
 +===== Features =====
 + 
 +  * 12 digital inputs
 +  * 10 relay outputs 8 A
 +  * 4 universal inputs/outputs
 +  * Ethernet, USB, IEX-2, 2×RS232
 +  * Enocean gateway (optional)
 +  * 24 VDC power supply   
 +
 +===== Safety standards =====
 +
 +EN 61010-1, EN 61010-2-201, EN 61131-2
 +
 +<WRAP pagebreak></WRAP>
 +
 +===== Technical specification =====
 +
 +|< 42% 45% >|
 +| System clock                                               100MHz|
 +| Instruction execution        |                      10ns per instruction |
 +| Program memory                                  896Kb for user program |
 +| Data memory                  |                    64Kb for user variables|
 +| Data retention                                                  7 days |
 +| RTC accuracy                               typ. ±2 sec per day at 25°C |
 +| Digital input (ix00..ix11)       24V 7mA, opto isolated, bidirectional |
 +| Digital input (ix12..ix15)       dry contact, internal pull-up 12V 3mA |
 +| Digital output (qx00..qx09)  |      relay 8A/250VAC or 8A/30VDC resistive|
 +| Digital output (qx12..qx15)  |     NPN transistor 30V 1A|
 +| IEX-2 bus load                   48 modules (Cybro + 47 IEX-2)|
 +| IEX-2 baud rate              |     20, 50, 100 (default), 250, 500kbps|
 +| IEX-2 cable length, 100kbps  |     100m (non-terminated)|
 +| IEX-2 cable length, 100kbps  |     300m (terminated)|
 +| IEX-2 cable length, 50kbps       500m (terminated)|
 +| Power supply                     24V (18..28V)|
 +| Power consumption            |  50mA (no load), 180mA (10 relays, 4x 10Vout)|
 +| Power output (IEX-2)             24V 2A (limited by resettable fuse)|
 +| Operating conditions             0..50°C, 0..85% rh non-condensing|
 +| Degree of protection             IP20|
 +| Installation category        |     III|
 +
 +===== Terminals =====
 +
 +{{en:hiq_hw:pasted:mc-24-05terminals.png}}
en/hiq_hw/mc3-24.1565788113.txt.gz · Last modified: 2019/08/14 13:08 by goran.kocjancic