User Tools

Site Tools


en:hiq_hw:mc3-24

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
en:hiq_hw:mc3-24 [2019/08/19 11:20] goran.kocjancicen:hiq_hw:mc3-24 [2023/01/24 15:13] (current) – [Technical specification] saso_santelj
Line 5: Line 5:
 <WRAP column 350px> <WRAP column 350px>
  
-{{ :en:hiq_hw:pasted:mc-24.png?nolink |}}+{{ :en:hiq_hw:pasted:mc-24-c3.png?nolink |}}
  
 </WRAP> </WRAP>
Line 11: Line 11:
 <WRAP column 600px> <WRAP column 600px>
  
-| Model number: ^ MC-24-01  | 24 VAC, 11 IO, Enocean, 2 × RS232, RS485, IEX2 terminals                 +| Model number: ^ MC-24-05  | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals                         
-| :::           ^ MC-24-02  | 24 VAC, 11 IO, 2 × RS232, RS485, IEX2 terminals                          | +| :::           ^ MC-24-06  | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals, EnOcean                
-| :::           ^ MC-24-03  | 24 VAC11 IO, Enocean, 2 × RS232, isolated RS485, IEX2 terminals        | +| Mounting:     | DIN rail(35mm), 6M, 106mm                                                                 ||
-| :::           ^ MC-24-04  | 24 VAC, 11 IO, 2 × RS232, isolated RS485, IEX2 terminals                 +
-| Mounting:     | DIN rail, 6M, 106mm                                                                 ||+
 | Dimensions:   | 106x108x58mm                                                                        || | Dimensions:   | 106x108x58mm                                                                        ||
  
Line 24: Line 22:
  
 ===== Features ===== ===== Features =====
- +  
-    Sources and consumers measurements: +  12 digital inputs 
-      1 × Grid +  10 relay outputs 8 A 
-      3 × Local power plants (PVwindcogeneration,...) +  4 universal inputs/outputs 
-      2 × Storage system (battery+  * EthernetUSBIEX-22×RS232 
-      4 × Consumers +  Enocean gateway (optional
-    * Load management +  24 VDC power supply   
-      * 4 × Consumers +
-      * Manual control +
-      * Manual override timer +
-      * Weekly timetable, 15 min resolution+
  
 ===== Safety standards ===== ===== Safety standards =====
  
-EN 50081-1, EN 61000-6-2, EN 61131-1, EN 61131-2, EN 61000-3-2, EN 61000-3-3+EN 61010-1, EN 61010-2-201, EN 61131-2
  
 <WRAP pagebreak></WRAP> <WRAP pagebreak></WRAP>
Line 44: Line 38:
 ===== Technical specification ===== ===== Technical specification =====
  
-|< 3540% >| +|< 4245% >| 
-Relay outputs:               |                                    8A/250V +System clock                                               100MHz| 
-Communication:               |    Ethernet2x RS2321x RS485, IEX-2 bus +| Instruction execution        |                      10ns per instruction | 
-Nominal power rating:                                            24 VDC +| Program memory                                  896Kb for user program | 
-| Power consumption:                            typ1W (no load), 10W max+| Data memory                  |                    64Kb for user variables| 
-| Power output:                |               24V 200mA (IEX-2 + terminals)| +| Data retention               |                                    7 days | 
-| Ingress protection:          |                                       IP20 +| RTC accuracy                               typ. ±2 sec per day at 25°C | 
-| Operating temperature:                                          0..45°C +| Digital input (ix00..ix11)       24V 7mA, opto isolated, bidirectional | 
-Storage temperature:         |                                  -20..75°C +| Digital input (ix12..ix15)       dry contact, internal pull-up 12V 3mA | 
-Relative humidity:                                           0..95% n/c |+| Digital output (qx00..qx09)  |      relay 8A/250VAC or 8A/30VDC resistive
 +Digital output (qx12..qx15)  |     NPN transistor 30V 1A| 
 +| IEX-2 bus load               |     48 modules (Cybro + 47 IEX-2)| 
 +| IEX-2 baud rate              |     2050100 (default)250, 500kbps| 
 +IEX-2 cable length, 100kbps  |     100m (non-terminated)
 +IEX-2 cable length, 100kbps      300m (terminated)| 
 +| IEX-2 cable length, 50kbps       500m (terminated)
 +| Power supply                     24V (18..28V)| 
 +| Power consumption            |  50mA (no load), 180mA (10 relays, 4x 10Vout)
 +| Power output (IEX-2)             24V 2A (limited by resettable fuse)
 +| Operating conditions             0..50°C, 0..85% rh non-condensing
 +Degree of protection         |     IP20
 +Installation category            III|
  
 ===== Terminals ===== ===== Terminals =====
  
 +{{en:hiq_hw:pasted:mc-24-05terminals.png}}
en/hiq_hw/mc3-24.1566213624.txt.gz · Last modified: 2019/08/19 11:20 by goran.kocjancic