en:hiq_hw:mc3-24 [2020/07/15 08:52] – [Technical specification] alen.mejaken:hiq_hw:mc3-24 [2023/01/24 15:13] (current) – [Technical specification] saso_santelj
Line 39: Line 39:
  
 |< 42% 45% >| |< 42% 45% >|
-| System clock                                               100MHz      |+| System clock                                               100MHz|
 | Instruction execution        |                      10ns per instruction | | Instruction execution        |                      10ns per instruction |
 | Program memory                                  896Kb for user program | | Program memory                                  896Kb for user program |
Line 45: Line 45:
 | Data retention                                                  7 days | | Data retention                                                  7 days |
 | RTC accuracy                               typ. ±2 sec per day at 25°C | | RTC accuracy                               typ. ±2 sec per day at 25°C |
-| Digital input (ix00..ix11)           |     24V 7mA, opto isolated, bidirectional |+| Digital input (ix00..ix11)   |     24V 7mA, opto isolated, bidirectional |
 | Digital input (ix12..ix15)       dry contact, internal pull-up 12V 3mA | | Digital input (ix12..ix15)       dry contact, internal pull-up 12V 3mA |
-| Digital output (qx00..qx09)     relay 8A/250VAC or 8A/30VDC resistive| +| Digital output (qx00..qx09)      relay 8A/250VAC or 8A/30VDC resistive| 
-| Digital output (qx12..qx15)  |     NPN transistor 30V 1A                 +| Digital output (qx12..qx15)  |     NPN transistor 30V 1A| 
-| IEX-2 bus load                   48 modules (Cybro + 47 IEX-2)         +| IEX-2 bus load                   48 modules (Cybro + 47 IEX-2)| 
-| IEX-2 baud rate              |     20, 50, 100 (default), 250, 500kbps   +| IEX-2 baud rate              |     20, 50, 100 (default), 250, 500kbps| 
-| IEX-2 cable length, 100kbps  |     100m (non-terminated)                 +| IEX-2 cable length, 100kbps  |     100m (non-terminated)| 
-| IEX-2 cable length, 100kbps  |     300m (terminated)                     +| IEX-2 cable length, 100kbps  |     300m (terminated)| 
-| IEX-2 cable length, 50kbps       500m (terminated)                     +| IEX-2 cable length, 50kbps       500m (terminated)| 
-| Power supply                     24V (18..28V)                         +| Power supply                     24V (18..28V)| 
-| Power consumption            |50mA (no load), 180mA (10 relays, 4x 10Vout) | +| Power consumption            |  50mA (no load), 180mA (10 relays, 4x 10Vout)| 
-| Power output (IEX-2)             24V 2A (limited by resettable fuse)   +| Power output (IEX-2)             24V 2A (limited by resettable fuse)| 
-| Operating conditions             0..50°C, 0..85% rh non-condensing     +| Operating conditions             0..50°C, 0..85% rh non-condensing| 
-| Degree of protection             IP20                                  +| Degree of protection             IP20| 
-| Installation category        |     III                                   |+| Installation category        |     III|
  
 ===== Terminals ===== ===== Terminals =====
  
 +{{en:hiq_hw:pasted:mc-24-05terminals.png}}
en/hiq_hw/mc3-24.1594803159.txt.gz · Last modified: 2020/07/15 08:52 by alen.mejak