-====== Three phase power-sensor ======+====== Three phase power sensor, CT ====== 
 + 
 +**3-phase power-sensor, current transformer** 
 + 
 +<WRAP column 350px> 
 + 
 +{{  :hiq_energy:hems:hardware:pm3-e-d_ct.png?nolink  |}} 
 + 
 +</WRAP> 
 + 
 +<WRAP column 300px> 
 + 
 +| Model number: ^ PM3-E-D-CT                                   | 
 +| Connect to:   | [[en:hiq_hw:mc-230|MC-230]]           | 
 +| :::           | RS485 power sensor bus A - B                 | 
 +| Mounting:     | DIN rail, 1M, 18 mm                          | 
 +| Dimensions:   | 65 × 72 × 94,5 mm                             |  
 + 
 +^ Used for measuring power and energy of                 || 
 +| ✔ | single/three-phase energy sources                        | 
 +| ✔ | single/three-phase energy consumers                      | 
 + 
 +</WRAP> 
 + 
 +<WRAP clear></WRAP> 
 + 
 +===== Applications ===== 
 + 
 +  * Digital multi-function power sensor for single/three phase networks 
 + 
 +===== Features ===== 
 + 
 +  * DIN rail mounting with 3x current transformers ([[en:hiq_hw:ct-3-e-xx|3-ph current transformer]]) 
 +  * Line voltage and THD% (total harmonic distortion) of all phases 
 +  * Line Frequency 
 +  * Currents, Current demands and current THD% of all phases 
 +  * Power, maximum power demand and power factor 
 +  * Active energy imported and exported 
 +  * Reactive energy imported and exported 
 + 
 +===== General description ===== 
 + 
 +The unit measures and displays the characteristics of three phase four wires(3p4w) supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported. 
 + Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60minutes.  
 +In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product.  
 +The requisite current input(s) are obtained via current transformers (CT). 
 +This power sensor can be configured to work with a wide range of CTs with 0.33V output, giving the unit a wide range of operation. Built-in interfaces provide pulse and RS485 Modbus RTU outputs. Configuration is password protected. 
 +This power sensor can be powered from a separate auxiliary (AC or DC) supply. Alternatively, it can be powered from the monitored supply, where appropriate. 
 + 
 +===== Technical specifications ===== 
 + 
 +|< 35% 40% >| 
 +^ Technical Data                                                               || 
 +| Operating Humidity                                                    ≤ 75% | 
 +| Storage Humidity                                                      ≤ 95% | 
 +| Operating Temperature          |                                -25°C - +50°C | 
 +| Storage Temperature            |                                -40°C - +70°C | 
 +| Mounting                                               DIN rail (DIN 43880) | 
 +| Sealing                        |                                  IP51 Indoor | 
 +| Auxiliary supply voltage                                       Nominal ± 1% | 
 +| Auxiliary supply frequency                                     Nominal ± 1% | 
 +| Frequency                      |                            50Hz or 60Hz(±2%) | 
 +| Power Consumption              |                                        ≤ 10W | 
 +^ Accuracy                                                                     || 
 +| Voltage, Current                                                       0.5% | 
 +| Frequency                      |                        0.2% of Mid-Frequency | 
 +| Power Factor                                             1% of Unity (0.01) | 
 +| Active Power, Apparent Power                          ± 1% of Range Maximum | 
 +| Reactive Power                                        ± 1% of Range Maximum | 
 +| Reactive Energy (Varh)                                ± 1% of Range Maximum | 
 +| Active Energy (Wh)                                      Class 1 IEC 62053-21| 
 +^ Current transformer                                                          || 
 +| Frequency                      |                                     50-60 Hz | 
 +| Rated current                  |                                         50 A | 
 +| Accuracy                                  from 20% to 120% of rated current | 
 +| Phase angle                    |  less than 2 degrees at 50% of rated current | 
 +| Insulation voltage                                                  600 VAC | 
 +| Maximum primary voltage        |               5000 VAC (insulated conductor) | 
 +| Dielectric strength            |                              2.5 kV/1mA/1min | 
 +| Operating temperature          |                                  -15 to 60°C | 
 +| Operating humidity                                                   < 85 % | 
 +| Case material                  |                                   PC/UL94-V0 | 
 +| Bobin                          |                                          PBT | 
 +| Core                                                              Permalloy | 
 +| Internal structure                                                    Epoxy | 
 +| Leads                          |                UL 1015, Twisted pair, 22 AWG | 
 +^ Modbus                                                                       || 
 +| Bus Type                                                RS485 (Semi-Duplex) | 
 +| Protocol                                                         Modbus RTU | 
 +| Baud Rate                      |                       1200/2400/4800/9600bps | 
 +| Address Range                  |                                        1-247 | 
 +| Max. Bus Loading                                                      64pcs | 
 +| Communication Distance                                          1000 Meters | 
 +| Parity                                                        EVEN/ODD/NONE | 
 +| Data Bit                                                                  8 | 
 +| Stop Bit                                                                  1 | 
 +                                                 
 +                                                 
 +                                                 
 +                                                 
 +                                                 
 +                                                 
 +                                                 
 +                                                 
 +                                                 
 +                                                 
 +<WRAP pagebreak></WRAP> 
 + 
 +===== Dimensions ===== 
 + 
 +{{:hiq_energy:hems:hardware:pm3-e_ct_dimensions.png?nolink|}} 
 + 
 +===== Installation ===== 
 + 
 +{{:hiq_energy:hems:hardware:pm3-e_instalation.png?nolink|}} 
 + 
 +{{ :hiq_energy:hems:hardware:hiq_pm3-e-d-ct_user_manual_v1.pdf |}} {{ :hiq_energy:hems:hardware:hiq_pm3-e-d-ct_protocol_v1.6.pdf |}} 
 + 
 + 
  