User Tools

Site Tools


en:hiq_hw:wr-1

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
en:hiq_hw:wr-1 [2022/11/29 13:57] gdzampoen:hiq_hw:wr-1 [2022/12/02 14:33] (current) – [Terminals and wiring] gdzampo
Line 17: Line 17:
 ===== Applications ===== ===== Applications =====
  
-  * Remote controlled relay. Act as modbus RTU slave. Optimal for long range, no hopping. Up to 8 releays per network. Protected private connection.+  * Remote controlled relay. Act as modbus RTU slave. Optimal for long range, no hopping.
  
 </WRAP> </WRAP>
Line 24: Line 24:
  
 ===== Installation and mounting ===== ===== Installation and mounting =====
-  * :!: Carefully open WR-1 module and configure serial communication with jumpers. (Default configuration is 9600bps, 8N1 with normal timeout)+  * :!: Carefully open WR-1 module and configure address with jumpers. (Default address is 200)
   * :!: Place WR-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.   * :!: Place WR-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.
-  * Connect RS485 terminals to WR-1 RS485 terminals +  * Connect relay terminals 
-    * A - A +
-    * B - B +
-    * C - GND+
   * Connect to 230V power supply   * Connect to 230V power supply
   * Configure radio pairing   * Configure radio pairing
  
-{{ hiq_hardware:wm1_module_diagram.png?nolink&0x500  }} +{{ hiq_hardware:wr-1_wiring.png?nolink&0x500  }} 
-{{ hiq_hardware:wm1_mounting.png?nolink&0x500  }}+{{ hiq_hardware:wr-1_dimension.png?nolink&0x500  }}
  
 <WRAP pagebreak></WRAP> <WRAP pagebreak></WRAP>
Line 40: Line 37:
 ===== Features ===== ===== Features =====
  
-  * replacement for RS485 wiring +  * remote controlled relay 
-  * Modbus RTU serial protocol +  * act as modbus RTU slave
-  * wired/wireless combinations+
   * very long range, no hopping   * very long range, no hopping
 +  * up to 8 relays per network
   * protected private connection   * protected private connection
-  * multiple slaves per device +  * multiple addressable groups 
-  * multiple addressable groups +
  
 ===== Technical specification ===== ===== Technical specification =====
  
-| Power supply:          |                                230V, 50/60Hz, 1W |+| Power supply:          |                       230V, 50/60Hz, 1W |
 | Ingress protection:    |                                    IP20 | | Ingress protection:    |                                    IP20 |
-| Operating temperature:                                -20..50°C |+| Operating temperature:                              -20..50°C |
 | Storage temperature:                                 -40..85°C | | Storage temperature:                                 -40..85°C |
-| Relative humidity:                                  0..85% n/c |+| Relative humidity:                                  0..85% n/c |  
 + Modbus   
 +| Address range:                               200..207 | 
 +| Relay mapping          |      coil 1(start address 00h) | 
 +| Data bits & parity          8n1 | 
 +| Supported functions    |      01 - read coil \\ 05 - write single coil \\ 15 - write multiple coils | 
 + Relay output 
 +| Nominal rating                               10A 250Vac (NO), 3A 250Vac (NC) | 
 +| (resistive)          |      5A 30Vdc (NO), 3A 30Vdc (NC) | 
 +Radio 
 +|Frequency band          |               ISM 868MHz (EU) | 
 +|Subband                  L 866.8MHz, 25mW, 1% utility | 
 +|Modulation              |  fSK 38.4kbps 80kHz bandwidth | 
 +|Listen before talk      |    yes, delay limited to 20ms | 
 +|Group address            32-bit, automatically generated | 
 +|Connection time          10s power-on to network ready | 
 +|Message delay            5ms from tx start to relay on | 
 +|Output power            |                           25mW | 
 +|Operating range          3..300m with optical visibility|
  
-===== Terminals and wiring ===== +===== Modbus address setting ===== 
 +Change is applied right away, no reset needed.
  
-| To power sensor ^ A | RS485 bus  | +{{ hiq_hardware:WR-1_address_settings.png?nolink&0x500  }}
-| :::            ^ B | :::        | +
-| :::            ^ C | :::        | +
-| To power supply ^ L| 230V AC | +
-| :::             ^ N| :::     | +
- +
-{{ hiq_hardware:wm1_wiring.png?nolink&0x200  }} +
- +
-<WRAP pagebreak></WRAP> +
- +
-===== Serial configuration and timeout ===== +
-  * Available baudrates 2400, 9600, 19200, 38400 bps +
-  * Data bits and parity 8N1, 7E1, 8E1, 8N2 +
-  * :!: Max 64 bytes per transmition +
-  * Integrated 240 Ohm termination resistor +
- +
-{{ hiq_hardware:wm1_serial.png?nolink&0x500  }}+
  
 ===== Radio pairing configuration ===== ===== Radio pairing configuration =====
Line 95: Line 93:
 {{ hiq_hardware:wm1_configuration_2.png?nolink&0x500  }} {{ hiq_hardware:wm1_configuration_2.png?nolink&0x500  }}
  
-==== Topology examples ====+==== Examples ====
      
-  * Modbus master, connected to 12 slaves using a pair of WM-1 devices 
-  * Modbus master, connected to 10 slaves, organized in two groups 
-  * Modbus master, connected to 5 slaves, each one having local WM-1 device 
  
-{{ hiq_hardware:wm1_topology.png?nolink&0x500  }}+{{ hiq_hardware:WR-1_examples.png?nolink&0x300  }}
  
-==== Multiple groups ==== 
-   
-  * When the system has two or more separate Modbus lines, they should be configured as separate groups.  
-  * Each group has a single master and one or more slaves. 
-  * Groups can't talk to each other, but they share the same bandwidth.  
-  * Two masters may start transmitting at the same time causing collisions.  
-  * To reduce number of missed messages, keep the traffic low. 
-   
- 
-{{ hiq_hardware:wm1_multiplegroups.png?nolink&0x500  }} 
  
 ===== Connection check ===== ===== Connection check =====
-  * Press button shortly +  * press the button shortly \\ 
-  * RF LED will blink shortly on each connected device +With each press of the button, the relay will 
-  * Serial interface is unaffected +switch on/off. Other devices are not affected.
  
-{{ hiq_hardware:wm1_connectioncheck.png?nolink&0x150  }}+{{ hiq_hardware:WR-1_relay_button.png?nolink&0x150  }}
  
 ===== Factory reset ===== ===== Factory reset =====
en/hiq_hw/wr-1.1669730269.txt.gz · Last modified: 2022/11/29 13:57 by gdzampo