 +==== Power plant connection ====
 +
 +The power plants can be connected to the grid in two ways:
 + 
 +|< 700px >|
 +^  serial with grid power sensor  |^  parallel with grid power sensor  |
 +|  {{ :hiq_energy:hems:hardware:connected_power_plant_in.png?direct400 |}}  ||  {{ :hiq_energy:hems:hardware:connected_power_plant_ex.png?direct400 |}} |
 +
 +When configuring the power plant, select
 +   ***in**: serial (**in**ternal) with grid power sensor
 +   ***ex**: parallel (**ex**ternal) with grid power sensor
 +The power plants are configured as internal by default.
 +
 ==== PV inverter ==== ==== PV inverter ====
  
-Monitoring of PV Inverter is possible by two ways:\\ +Obtaining relevant data from photovoltaic is possible by two ways:\\ 
-1. adding of power-sensor to measure produced electricity. How to add power sensor please see\\+1. adding power-sensor to measure produced electricity by PV (no connection to interver) - on how to add power sensor please see [[en:robotina_charger:commissioning:power_sensor|Power Sensor]]\\
 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters) 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters)
  
-=== One-phase sensor PM1-E-D ===+=== EVSE and PV inverter connection === 
 + 
 +|< 700px >| 
 +|  {{ :hiq_energy:robotina_charger:rc_pv_inverter_connection_router.png?direct&800|}} 
 + 
 +To add inverter on HEMS configurator: 
 +  *   on settings page inside source table, select SolarEdge inverter. Please see [[en:robotina_charger:software#settings|]] 
 +  *   on io mux page set IP address for inverter. Please see [[en:robotina_charger:software#io_mux|]]  
 + 
 +To setup Modbus TCP on Inverter using SetApp: 
 +  *   Select Site Communication menu  
 +     * RS485-1 -> Protocol -> SunSpec (Non-SE Logger) 
 +     * RS485-1 -> Device ID, and enter the number 1 
 +     * Modbus TCP and set to Enable 
 +     * set TCP port to 502
  
-    **Connect** communication bus (to only one power-sensor) +**Note**:\\ The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes.\\ It is important to follow rules above, firstly to set HEMS configurator following Inverter setup due to 2 minutes time frame.
-  *   In HEMS Configurator power-sensor should appear as a "new device" +
-  *   Press and hold the push-button on the power-sensor until it appears **-SEt-** on display +
-  *   In HEMS Configurator click on the **" add"** button next to the source or consumer that the sensor is measuring +
-  *   Connect communication bus to the next power-sensor and repeat procedure+