 Obtaining relevant data from photovoltaic is possible by two ways:\\ Obtaining relevant data from photovoltaic is possible by two ways:\\
-1. adding power-sensor to measure produced electricity by PV (no connection to interver). How to add power sensor please see [[en:robotina_charger:commissioning:power_sensor|Power Sensor]]\\+1. adding power-sensor to measure produced electricity by PV (no connection to interver) - on how to add power sensor please see [[en:robotina_charger:commissioning:power_sensor|Power Sensor]]\\
 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters) 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters)
  
-=== SolarEdge inverter over Modbus TCP ===+=== EVSE and PV inverter connection ===
  
-  *   **Connect** communication bus (to only one power-sensor) +|< 700px >| 
-  *   In HEMS Configurator power-sensor should appear as a "new device" +|  {{ :hiq_energy:robotina_charger:rc_pv_inverter_connection_router.png?direct&800|}} 
-  *   Press and hold the push-button on the power-sensor until it appears **-SEt-** on display + 
-    In HEMS Configurator click on the **" add"** button next to the source or consumer that the sensor is measuring +To add inverter on HEMS configurator: 
-  *   Connect communication bus to the next power-sensor and repeat procedure+  *   on settings page inside source table, select SolarEdge inverter. Please see [[en:robotina_charger:software#settings|]] 
 +  *   on io mux page set IP address for inverter. Please see [[en:robotina_charger:software#io_mux|]]  
 + 
 +To setup Modbus TCP on Inverter using SetApp: 
 +  *   Select Site Communication menu  
 +     * RS485--> Protocol -> SunSpec (Non-SE Logger) 
 +     RS485--> Device ID, and enter the number 1 
 +     Modbus TCP and set to Enable 
 +     set TCP port to 502 
 + 
 +**Note**:\\ The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes.\\ It is important to follow rules above, firstly to set HEMS configurator following Inverter setup due to 2 minutes time frame.