 Obtaining relevant data from photovoltaic is possible by two ways:\\ Obtaining relevant data from photovoltaic is possible by two ways:\\
-1. adding power-sensor to measure produced electricity by PV (no connection to interver). How to add power sensor please see [[en:robotina_charger:commissioning:power_sensor|Power Sensor]]\\+1. adding power-sensor to measure produced electricity by PV (no connection to interver) - on how to add power sensor please see [[en:robotina_charger:commissioning:power_sensor|Power Sensor]]\\
 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters) 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters)
  
-=== SolarEdge inverter over Modbus TCP ===+=== EVSE and PV inverter connection ===
  
 |< 700px >| |< 700px >|
-^ EVSE and PV inverter connection | 
 |  {{ :hiq_energy:robotina_charger:rc_pv_inverter_connection_router.png?direct&800|}}  | |  {{ :hiq_energy:robotina_charger:rc_pv_inverter_connection_router.png?direct&800|}}  |
  
 +To add inverter on HEMS configurator:
 +  *   on settings page inside source table, select SolarEdge inverter. Please see [[en:robotina_charger:software#settings|]]
 +  *   on io mux page set IP address for inverter. Please see [[en:robotina_charger:software#io_mux|]] 
  
 +To setup Modbus TCP on Inverter using SetApp:
 +  *   Select Site Communication menu 
 +     * RS485-1 -> Protocol -> SunSpec (Non-SE Logger)
 +     * RS485-1 -> Device ID, and enter the number 1
 +     * Modbus TCP and set to Enable
 +     * set TCP port to 502
  
- +**Note**:\\ The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes.\\ It is important to follow rules above, firstly to set HEMS configurator following Inverter setup due to 2 minutes time frame.
-    **Connect** communication bus (to only one power-sensor) +
-  *   In HEMS Configurator power-sensor should appear as a "new device" +
-  *   Press and hold the push-button on the power-sensor until it appears **-SEt-** on display +
-  *   In HEMS Configurator click on the **" add"** button next to the source or consumer that the sensor is measuring +
-  *   Connect communication bus to the next power-sensor and repeat procedure+
en/robotina_charger/commissioning/pv_inverter.1670586015.txt.gz · Last modified: 2022/12/09 11:40 by gdzampo