====== Manufacture ====== ===== HC-IQ ===== FW: {{ hiq_energy:goflex_hems:downloads:goflex_hems_v1.0.0.cyp |}} ===== GW-WN-W ===== Configure **DIP SW** to **1 = ON, 2 - 8 = OFF** ===== Power-meters ===== Modbus settings for power-meters we supply: **9600 8n2; ID: 149** ==== Eastron ==== Factory setting: **2400 8n1; ID: 1** Put power-meter in set mode by pressing button until -SET- is displayed on power-meter display. | Parameter | Address (hex) | Format | Default value (hex) | New value (hex) | | Parity / Stop bits | 40019 (00 12) | float | 0 (00 00 00 00) = n1 | 3 (40 40 00 00) = n2 | | Meter ID | 40021 (00 14) | float | 1 (3F 80 00 00) = 1 | 149 (43 15 00 00) = 149 | | Baud Rate | 40029 (00 1C) | float | 0 (00 00 00 00) = 2400 | 2 (40 00 00 00) = 9600 | CyBro-2-230-E configuring SW: {{ hiq_energy:goflex_hems:downloads:eastron_config.zip |}} ==== Iskra ==== Power-meters are supplied according to our specifications - no configuration needed before sending. ===== AiR-12 ===== Set **NAD** to **700** ===== TS-H ===== Set **NAD** to **800 - 807**