====== HIQ designing ====== Presented electric wiring plans were made with the help of [[http://www.3xm.se/index_eng.html| Elwin]] software which is made by [[http://www.3xm.se/automation_main_eng.htm|3xM Automation company]]. New plans can be made with modification of included {{hiq_building_automation:hiq_home:methods:designing:hiq_wiring_ewa.zip|Elwin project }} or with modification of {{hiq_building_automation:hiq_home:methods:designing:hiq_wiring_dxf.zip| DXF plans }}with any DXF capable program. With the Elwin project, all HIQ symbols are included. The whole design plan can be also downloaded as a {{hiq_building_automation:hiq_home:methods:designing:hiq_wiring.pdf| PDF file}}. ===== Page 1- Power distribution-RCD switch and power meter ===== Single phase power input, connection of RCD switch (Residual Current Device) and [[en:hiq_hw:pm-1-iq|power meter]].\\ Input can be single or three phase. \\ The [[en:hiq_hw:pm-1-iq| power meter]] on the wiring plan is connected to measure the whole electricity consumption, but can be connected to any device (or group of devices). Only single phase electricity measurement is available.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing01.png?nolink&800}}\\ ===== Page 2-3 - Power distribution - Fuses ===== Suggested fuse plan.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing02.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing03.png?nolink&800}}\\ ===== Page 4 - Control System-Power supply, HC, CAD-232 ===== [[en:hiq_hw:ps-iq|24V power supply (PS) ]] for control system, [[en:hiq_hw:hc-iq| Home controller]] and [[en:hiq_hw:pm-1-iq| CAD-232-A2-IQ]]. \\ [[en:hiq_hw:ps-iq|24V power supply ]] can be optionally used for LED lighting (up to 2.5A with serial power supply, larger power supply can be used). \\ [[en:hiq_hw:hc-iq| Home controller (HC) ]] is the heart of the system. It is connected to the network (ETH) and has optional inputs (connections are on page [[en:hiq_home:methods:design#page_15_home_controller_inputs|15]]) and outputs (connections are on page [[en:hiq_home:methods:design#page_16_home_controller_outputs|16]]).\\ [[en:hiq_hw:pm-1-iq|CAD-232-A2-IQ]] expander is used as communication interface between home controller and power meter (If power meter is not used then the expander is not necessary). It is connected to a home controller through IEX bus, to COM2 on home controller input and to power meter (RS485 communication).\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing04.png?nolink&800}}\\ ===== Page 5-6 - CS-Light controller 00 and 01 ===== [[en:hiq_home:hardware:lc-10-iq|Light controllers (LC)]] are connected to IEX bus, we can connect up to up 4 LC to 1 home controller. On the top side are inputs and on the bottom side are outputs (connections are on page [[en:hiq_home:methods:design#page_17-24_light_controller|17-24]]). \\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing05.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing06.png?nolink&800}}\\ ===== Page 7 – CS - Light dimmer ===== Up to 4 light dimmers can be connected to 1 HC. On sample plan we use 2 [[en:hiq_hw:ld-p4-iq|Light dimmers drivers]] for [[en:hiq_hw:lud12-iq|LUD-12]] universal light dimmers.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing07.png?nolink&800}}\\ ===== Page 8 – CS - Blinds controllers ===== Up to 2 [[en:hiq_hw:bc-5-iq|Blinds controllers (BC)]] can be connected to 1 HC.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing08.png?nolink&800}}\\ ===== Page 9 – CS - bus extender, LED light dimmer ===== [[en:hiq_hw:cad-be-prot-iq| Bus extender (BE)]] is a passive switch for easy IEX bus interconnection between cabinet and field modules.\\ \\ Up to 4 light dimmers can be connected to 1 HC. On sample plan we use 2 [[en:hiq_home:hardware:ld-v4-iq|LED stripe dimmers]].\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing09.png?nolink&800}}\\ ===== Page 10 – CS - Scene controllers ===== Up to 4 Scene Controllers can be connected to 1 HC. On sample plan are 4 [[en:hiq_hw:sc-4t-iq|Scene Touch Panels]], but also [[en:hiq_hw:sc-4o-iq|Scene Panels]] and [[en:hiq_hw:sc-4s-iq|Scene controllers]] can be connected in the same way.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing10.png?nolink&800}}\\ ===== Page 11-12 - CS - Thermostats ===== Up to 5 Thermostats can be connected to 1 HC. On sample plan we use 5 [[en:hiq_hw:th-1t-iq|Touch buttons electronic thermostats]], but also ordinary [[en:hiq_hw:th-1m-iq|Electronic thermostats]] and [[en:hiq_hw:th-2-iq|Blind electronic thermostats]] can be connected in a similar way.\\ \\ Optionally we can connect window switch on each thermostat (sample on –TH02 and -TH03) (not possible with [[en:hiq_hw:th-2-iq|Blind electronic thermostat]]).\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing11.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing12.png?nolink&800}}\\ ===== Page 13 - CS-Fan-coil ===== Up to 5 [[en:hiq_hw:fc-1-iq| Fan-coil controllers (FC)]] can be connected to 1 HC. On our sample plan we have 3 FC, 2 thermostats are controlling radiator valves ([[en:hiq_home:methods:design#page_36-38_fan-coil|page 36-38]]).\\ \\ FC controllers are the last items on IEX bus. Longer IEX bus lines (over 100m) must be terminated with a 120ohm resistor between CANL and CANH (-R1).\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing13.png?nolink&800}}\\ ===== Page 14 - CS-Blank page ===== Blank page for future extensions.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing14.png?nolink&800}}\\ ===== Page 15 – Home controller inputs ===== If used, optional [[en:hiq_hw:rhkf-u| lightness sensor]] must be connected to IW0 analog input on [[en:hiq_hw:hc-iq|home controller]]. \\ All other inputs are left for custom programming solutions (10 digital inputs IX0-IX7, IX8A, IX9B and 3 8-bit analog inputs IW1-IW3).\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing15.png?nolink&800}}\\ ===== Page 16 – Home controller outputs ===== QX0-QX4 outputs – can be used for radiator valves or to control other heating/cooling devices. Internal relay is used for valves, other loads are recommended to use an additional 16A installation relay.\\ In our plan we use 2 radiator valves (and 3 [[en:hiq_hw:fc-1-iq| Fan-coil controllers]]).\\ QX5 output – is used for Air Conditioner.\\ QX6 output – is used for Boiler.\\ QX7 output – is used for Chiller.\\ All three outputs are connected to external installation relays (-K.A, -K.B and -K.C) .\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing16.png?nolink&800}}\\ ===== Page 17-24 – Light controller ===== Lights and managed power sockets are connected to [[en:hiq_home:hardware:lc-10-iq|Light controllers ]] . \\ Several button combinations are possible.\\ Managed power sockets should be connected through installation relays (-K12-K14, -K22-K23 and -K30-K33).\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing17.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing18.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing19.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing20.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing21.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing22.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing23.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing24.png?nolink&800}}\\ ===== Page 25-27 – Power sockets ===== A sample plan assumes use of managed and unmanaged sockets. Managed sockets are connected to [[en:hiq_home:hardware:lc-10-iq|Light controllers]]. External installation relays should be used on Light controller outputs.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing25.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing26.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing27.png?nolink&800}}\\ ===== Page 28-29 – Light dimmers ===== On sample plan we use 2 [[en:hiq_hw:ld-p4-iq|Light dimmers drivers]]. On each driver we can connect up to 4 [[en:hiq_hw:lud12-iq|LUD-12]] universal light dimmers.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing28.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing29.png?nolink&800}}\\ ===== Page 30-33 – Blinds controllers ===== On our sample plan we have 2 [[en:hiq_hw:bc-5-iq|Blinds controllers (BC)]] with 9 blinds and 9 double-push buttons.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing30.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing31.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing32.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing33.png?nolink&800}}\\ ===== Page 34-35 – LED stripe dimmer ===== On sample plan we use 2 [[en:hiq_home:hardware:ld-v4-iq|LED stripe dimmers]]. RGBW (red-green-blue-white) LED stripe is connected on the first dimmer and the second dimmer controls 2 white LED stripes (2 outputs are empty). 2 push buttons are connected on the second dimmer.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing34.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing35.png?nolink&800}}\\ ===== Page 36-38 – Fan-coil ===== [[en:hiq_hw:fc-1-iq|Fan-coil]] connection.\\ \\ {{hiq_building_automation:hiq_home:methods:designing:designing36.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing37.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing38.png?nolink&800}}\\