====== Master Controller ======
**Advanced Controller**
{{:en:hiq_hw:pasted:mc-230.png}}
| Model number: ^ MC-230-01 | 230 VAC, 11 IO, Enocean, 2 × RS232, RS485, IEX2 terminals |
| ::: ^ MC-230-02 | 230 VAC, 11 IO, 2 × RS232, RS485, IEX2 terminals |
| ::: ^ MC-230-03 | 230 VAC, 11 IO, Enocean, 2 × RS232, isolated RS485, IEX2 terminals |
| ::: ^ MC-230-04 | 230 VAC, 11 IO, 2 × RS232, isolated RS485, IEX2 terminals |
| Mounting: | DIN rail (35mm), 6M, 106mm ||
| Dimensions: | 106x108x58mm ||
===== Features =====
* 3 digital inputs
* 4 relay outputs 8 A
* 4 universal inputs/outputs
* Ethernet, USB, IEX-2, 2×RS232, 1×RS485 (optional isolated)
* Enocean gateway (optional)
* 230 VAC or 24 VDC power supply (use only one option!)
===== Safety standards =====
EN 61010-1, EN 61010-2-201, EN 61131-2
===== Technical specification =====
|< 35% 40% >|
| Relay outputs: | 8A/250VAC resistive, 8A/30VDC resistive |
| Communication: | Ethernet, 2x RS232, 1x RS485, IEX-2 bus |
| Nominal power rating: | 230 VAC or 24 VDC|
| Power consumption: | typ. 1W (no load), 10W max|
| Power output: | 24V 200mA (with 230 VAC power supply)|
| Ingress protection: | IP20 |
| Operating temperature: | 0..50°C |
| Storage temperature: | -20..75°C |
| Relative humidity: | 0..85% n/c |
| Input type(ix00..ix02): | dry contact, internal pull-up 12V 2mA |
| Cable lenght: | 50m|
| COM1 type | RS485 two wire |
| Transmit/receive | automatic switching |
| | |
| MAX recommended output power per relay: | |
| - incandescent / halogen 230V | 800 W|
| - halogen 12 V with transformer | 400 W|
| - fluorescent with electronic ballast | 400 W|
| - parallel compensated fluo lamps | 250 W / 30 uF|
| - electric heater | 1400 W|
| Total output power (all relays): | 4000 W|
===== Terminals =====