====== Master Controller ====== **Advanced Controller** {{ :en:hiq_hw:pasted:mc-24-c3.png?nolink |}} | Model number: ^ MC-24-05 | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals | | ::: ^ MC-24-06 | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals, EnOcean | | Mounting: | DIN rail(35mm), 6M, 106mm || | Dimensions: | 106x108x58mm || ===== Features ===== * 12 digital inputs * 10 relay outputs 8 A * 4 universal inputs/outputs * Ethernet, USB, IEX-2, 2×RS232 * Enocean gateway (optional) * 24 VDC power supply ===== Safety standards ===== EN 61010-1, EN 61010-2-201, EN 61131-2 ===== Technical specification ===== |< 42% 45% >| | System clock | 100MHz| | Instruction execution | 10ns per instruction | | Program memory | 896Kb for user program | | Data memory | 64Kb for user variables| | Data retention | 7 days | | RTC accuracy | typ. ±2 sec per day at 25°C | | Digital input (ix00..ix11) | 24V 7mA, opto isolated, bidirectional | | Digital input (ix12..ix15) | dry contact, internal pull-up 12V 3mA | | Digital output (qx00..qx09) | relay 8A/250VAC or 8A/30VDC resistive| | Digital output (qx12..qx15) | NPN transistor 30V 1A| | IEX-2 bus load | 48 modules (Cybro + 47 IEX-2)| | IEX-2 baud rate | 20, 50, 100 (default), 250, 500kbps| | IEX-2 cable length, 100kbps | 100m (non-terminated)| | IEX-2 cable length, 100kbps | 300m (terminated)| | IEX-2 cable length, 50kbps | 500m (terminated)| | Power supply | 24V (18..28V)| | Power consumption | 50mA (no load), 180mA (10 relays, 4x 10Vout)| | Power output (IEX-2) | 24V 2A (limited by resettable fuse)| | Operating conditions | 0..50°C, 0..85% rh non-condensing| | Degree of protection | IP20| | Installation category | III| ===== Terminals ===== {{en:hiq_hw:pasted:mc-24-05terminals.png}}