Commissioning
Control system
Power meters
Connect only one new power meter at the time.
In HIQ HEMS Configurator go to settings page. New power-meter should be detected (Address and Type should be displayed).
Long-press button on power meter until -SET- is displayed.
Press New address and enter new address according to following table.
Device | Address |
Grid | 150 |
|
1st power plant | 154 |
2nd power plant | 155 |
3rd power plant | 156 |
|
1st storage | 157 |
2nd storage | 158 |
|
1st consumer | 160 |
2nd consumer | 161 |
… | … |
8th consumer | 167 |
Load managers
Add new device
In HIQ HEMS Configurator go to wireless page
Click on device which will be added
Wait for network open - waiting device status.
Press button on device.
Wait until device is addressed and configured.
Procedure can be interrupted with “close network” button.
Remove device
Reset device:
power off wireless device for a few seconds.
After powering on wait for a few seconds for device to boot on.
Press and hold button, LED indicator will go off, then green and at the end red.
Release button.
In HIQ HEMS Configurator go to wireless page
Reset device should have error state (yellow sign with exclamation)
Click on reset device to clear place.
Control devices
In HIQ HEMS Configurator go to wireless page
Press icon for control device (wireless enocean push-button) to be configured
On control device press 0 (off) button
On control device press 1 (on) button
Sensors
Add new sensor
Adjust sensor address with DIP-switches according following table
In HIQ HEMS Configurator click on sensor which will be added
Wait for network open - waiting device status
Power on and pres button on sensor
Wait until sensor is configured
Procedure can be interrupted with “close network” button.
Sensor | Address | DIP switch settings |
S1 | 60 | |
S2 | 61 | |
S3 | 62 | |
S4 | 63 | |
S5 | 64 | |
S6 | 65 | |
S7 | 66 | |
S8 | 67 | |
Remove sensor
Reset sensor:
Power off sensor for few seconds
Reconnect sensor power supply
After sensor power on (but within 20 sec) press and hold button for at least 6 sec
In HIQ HEMS Configurator reset device should show error
Click on error icon to free occupied space