Wireless Modbus-to-Modbus bridge
Model number: | WM-1 |
---|---|
Frequency: | ISM 868MHz (EU) |
Dimensions: | 93x45x27 mm |
Power supply: | 230V, 50/60Hz, 1W |
Ingress protection: | IP20 |
Operating temperature: | -20..50°C |
Storage temperature: | -40..85°C |
Relative humidity: | 0..85% n/c |
To power sensor | A | RS485 bus |
---|---|---|
B | ||
C | ||
To power supply | L | 230V AC |
N |
* turn on all devices at the same time * within 10 seconds, while RF LED is blinking, press and hold button on one of the devices * after a second, the new address is randomly generated and sent to all devices. RF LED will blink 3 times to confirm the new address.
* turn on the device * within 10 seconds, press and hold button on one of the existing devices * after a second, the existing group address is sent to the new device. RF LED will blink 3 times to confirm the address is sent.
* Modbus master, connected to 12 slaves using a pair of WM-1 devices * Modbus master, connected to 10 slaves, organized in two groups * Modbus master, connected to 5 slaves, each one having local WM-1 device
* When the system has two or more separate Modbus lines, they should be configured as separate groups. * Each group has a single master and one or more slaves. * Groups can't talk to each other, but they share the same bandwidth. * Two masters may start transmitting at the same time causing collisions. * To reduce number of missed messages, keep the traffic low.