en:goflex_hems:methods_resources:manufacture
Table of Contents
Manufacture
HC-IQ
GW-WN-W
Configure DIP SW to 1 = ON, 2 - 8 = OFF
Power-meters
Modbus settings for power-meters we supply: 9600 8n2; ID: 149
Eastron
Factory setting: 2400 8n1; ID: 1
Put power-meter in set mode by pressing button until -SET- is displayed on power-meter display.
Parameter | Address (hex) | Format | Default value (hex) | New value (hex) |
Parity / Stop bits | 40019 (00 12) | float | 0 (00 00 00 00) = n1 | 3 (40 40 00 00) = n2 |
Meter ID | 40021 (00 14) | float | 1 (3F 80 00 00) = 1 | 149 (43 15 00 00) = 149 |
Baud Rate | 40029 (00 1C) | float | 0 (00 00 00 00) = 2400 | 2 (40 00 00 00) = 9600 |
CyBro-2-230-E configuring SW: eastron_config.zip
Iskra
Power-meters are supplied according to our specifications - no configuration needed before sending.
AiR-12
Set NAD to 700
TS-H
Set NAD to 800 - 807