User Tools

Site Tools


en:hiq_hotel:grms_examples

GRMS examples

Standard with touch panels

Functionalities

Standard GRMS functionalities:

  • Master contactor
    • Disconnects all power outlets in room except fridge
  • Courtesy light (entrance, ON/OFF)
  • Lights:
    • ON/OFF 230 VAC - Toilet ceiling and mirror (parallel)
    • ON/OFF 230 VAC - Entrance
    • Dimmable 230 VAC - Room ceiling
    • Dimmable LED strip - Room wall above windows
    • Desk and bed side lights are powered from power outlets and thus are not directly individual controlled
  • HVAC
    • 0..10 V fan-coil

Hardware

ID Location Description Code
1 GRMS distribution board Master Controller MC-230-2
Mains disconnector
RCCB
Circuit breakers
Power relay
Light driver LUD12-IQ
Dimmable LED power supply
2 On-wall - main entrance Key-card holder KH-HI
3 Door (built in) Reed door sensor
4 Ceiling - entrance PIR motion sensor
5 On-Wall - toilet entrance 2 x Touch button B2-HI
- (1) = toilet light
- (2) = entrance light
6 On-Wall - room entrance 4 × Touch buttons B4-HI
- (1) = entrance light
- (2) = room ceiling light
- (3) = room wall light
- (4) = all off / room wall light to min
7 On-wall - bed side 4 × Touch buttons B4-HI
- (1) = entrance light
- (2) = room ceiling light
- (3) = room wall light
- (4) = all off / room wall light to min
8 On-wall - room entrance Touch Thermostat TH-HI

Upgrades

Functionalities

Additional optional GRMS functionalities:

  • Room info panels
    • Do Not Disturb (DND), Make Up Room (MUR)
    • Door-bell
  • Lighting
    • Individual control for all lights including desk and bed side lights
  • Curtain control (motorized 230 VAC curtain)
  • Toilet fan

Additional / Replaced Hardware

ID Location Description Code
1 GRMS distribution board GRMS expansion HR-EX-IQ
9 On-Wall - room entrance In room info panel IP-HI
10 On-Wall - room entrance Door bell DB-HI
11 On-Wall - corridor in front of the entrance Room info panel CP-HI
6 On-Wall - room entrance 6 × Touch buttons B6-HI
- (1) = entrance light
- (2) = room ceiling light
- (3) = room wall light
- (4) = curtain open
- (5) = curtain close
- (6) = all off, curtain close / room wall light to min
7 On-wall - bed side 6 × Touch buttons B6-HI
- (1) = entrance light
- (2) = room ceiling light
- (3) = room wall light
- (4) = right bedside light
- (5) = left bedside light
- (6) = all off, curtain close / room wall light to min
12 On-Wall - next to desk 2 × Touch buttons B2-HI
- (1) = desk light
- (2) = all off / room wall light to min

Standard with classic push-buttons

Functionalities

Standard GRMS functionalities:

  • Master contactor
    • Disconnects all power outlets in room except fridge
  • Courtesy light (entrance, ON/OFF)
  • Lights:
    • ON/OFF 230 VAC - Toilet ceiling and mirror (parallel)
    • ON/OFF 230 VAC - Entrance
    • Dimmable 230 VAC - Room ceiling
    • Dimmable LED strip - Room wall above windows
    • Desk and bed side lights are powered from power outlets and thus are not directly individual controlled
  • HVAC
    • 0..10 V fan-coil

Hardware

ID Location Description Code
1 GRMS distribution board Master Controller MC-230-2
Push-buttons expansion PB-IQ
Mains disconnector
RCCB
Circuit breakers
Power relay
Light driver LUD12-IQ
Dimmable LED power supply
2 On-wall - main entrance Key-card holder, basic (dry contact)
3 Door (built in) Reed door sensor
4 Ceiling - entrance PIR motion sensor
5 On-Wall - toilet entrance 2 x NO push-buttons
- (1) = toilet light
- (2) = entrance light
6 On-Wall - room entrance 4 × NO push-buttons
- (1) = entrance light
- (2) = room ceiling light
- (3) = room wall light
- (4) = all off / room wall light to min
7 On-wall - bed side 4 × NO push-buttons
- (1) = entrance light
- (2) = room ceiling light
- (3) = room wall light
- (4) = all off / room wall light to min
8 On-wall - room entrance Touch Thermostat TH-1T-IQ
en/hiq_hotel/grms_examples.txt · Last modified: 2019/08/22 09:05 by goran.kocjancic