en:hiq_hw:mc-230 [2019/08/19 11:48] goran.kocjancicen:hiq_hw:mc-230 [2021/11/19 14:17] (current) gdzampo
Line 9: Line 9:
 </WRAP> </WRAP>
  
-<WRAP column 600px>+<WRAP column 650px>
  
 | Model number: ^ MC-230-01  | 230 VAC, 11 IO, Enocean, 2 × RS232, RS485, IEX2 terminals             | | Model number: ^ MC-230-01  | 230 VAC, 11 IO, Enocean, 2 × RS232, RS485, IEX2 terminals             |
Line 15: Line 15:
 | :::           ^ MC-230-03  | 230 VAC, 11 IO, Enocean, 2 × RS232, isolated RS485, IEX2 terminals    | | :::           ^ MC-230-03  | 230 VAC, 11 IO, Enocean, 2 × RS232, isolated RS485, IEX2 terminals    |
 | :::           ^ MC-230-04  | 230 VAC, 11 IO, 2 × RS232, isolated RS485, IEX2 terminals             | | :::           ^ MC-230-04  | 230 VAC, 11 IO, 2 × RS232, isolated RS485, IEX2 terminals             |
-| Mounting:     | DIN rail, 6M, 106mm                                                               ||+| Mounting:     | DIN rail (35mm), 6M, 106mm                                                               ||
 | Dimensions:   | 106x108x58mm                                                                      || | Dimensions:   | 106x108x58mm                                                                      ||
  
Line 28: Line 28:
   * 4 relay outputs 8 A   * 4 relay outputs 8 A
   * 4 universal inputs/outputs   * 4 universal inputs/outputs
-  * Ethernet, USM, IEX-2, 2×RS232, 1×RS485 (optional isolated)+  * Ethernet, USB, IEX-2, 2×RS232, 1×RS485 (optional isolated)
   * Enocean gateway (optional)   * Enocean gateway (optional)
-  * 230 VAC power supply   +  * 230 VAC or 24 VDC power supply (use only one option!)
  
 ===== Safety standards ===== ===== Safety standards =====
  
-EN 50081-1, EN 61000-6-2, EN 61131-1, EN 61131-2, EN 61000-3-2, EN 61000-3-3+EN 61010-1, EN 61010-2-201, EN 61131-2
  
 <WRAP pagebreak></WRAP> <WRAP pagebreak></WRAP>
Line 41: Line 41:
  
 |< 35% 40% >| |< 35% 40% >|
-| Relay outputs:                                                  8A/250V |+| Relay outputs:                  8A/250VAC resistive, 8A/30VDC resistive |
 | Communication:                  Ethernet, 2x RS232, 1x RS485, IEX-2 bus | | Communication:                  Ethernet, 2x RS232, 1x RS485, IEX-2 bus |
-| Nominal power rating:        |                                    230 VAC |+| Nominal power rating:        |                           230 VAC or 24 VDC|
 | Power consumption:                            typ. 1W (no load), 10W max| | Power consumption:                            typ. 1W (no load), 10W max|
-| Power output:                |               24V 200mA (IEX-2 + terminals)|+| Power output:                |       24V 200mA (with 230 VAC power supply)|
 | Ingress protection:          |                                       IP20 | | Ingress protection:          |                                       IP20 |
-| Operating temperature:                                          0..45°C |+| Operating temperature:                                          0..50°C |
 | Storage temperature:                                          -20..75°C | | Storage temperature:                                          -20..75°C |
-| Relative humidity:                                           0..95% n/c | +| Relative humidity:                                           0..85% n/c | 
- +| Input type(ix00..ix02):      |      dry contact, internal pull-up 12V 2mA | 
 +| Cable lenght:                |                                         50m| 
 +| COM1 type                    |                             RS485 two wire | 
 +| Transmit/receive                                    automatic switching | 
 +|                              |                                            | 
 +| MAX recommended output power per relay:    |                              | 
 +| - incandescent / halogen 230V                                 800 W| 
 +| - halogen 12 V with transformer                               400 W| 
 +| - fluorescent with electronic ballast |                         400 W| 
 +| - parallel compensated fluo lamps                     250 W / 30 uF| 
 +| - electric heater                                            1400 W| 
 +| Total output power (all relays):      |                        4000 W|
  
 +<WRAP pagebreak></WRAP>
 ===== Terminals ===== ===== Terminals =====
  
 +{{:en:hiq_hw:pasted:mc-230-01_terminals.png}}
  