en:hiq_hw:wr-1 [2022/11/29 14:36] – [Technical specification] gdzampoen:hiq_hw:wr-1 [2022/12/02 14:33] (current) – [Terminals and wiring] gdzampo
Line 24: Line 24:
  
 ===== Installation and mounting ===== ===== Installation and mounting =====
-  * :!: Carefully open WR-1 module and configure serial communication with jumpers. (Default configuration is 9600bps, 8N1 with normal timeout)+  * :!: Carefully open WR-1 module and configure address with jumpers. (Default address is 200)
   * :!: Place WR-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.   * :!: Place WR-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.
-  * Connect RS485 terminals to WR-1 RS485 terminals +  * Connect relay terminals 
-    * A - A +
-    * B - B +
-    * C - GND+
   * Connect to 230V power supply   * Connect to 230V power supply
   * Configure radio pairing   * Configure radio pairing
Line 53: Line 50:
 | Operating temperature: |                               -20..50°C | | Operating temperature: |                               -20..50°C |
 | Storage temperature:                                 -40..85°C | | Storage temperature:                                 -40..85°C |
-| Relative humidity:                                  0..85% n/c | \\+| Relative humidity:                                  0..85% n/c | 
  Modbus    Modbus  
 | Address range:                               200..207 | | Address range:                               200..207 |
Line 60: Line 57:
 | Supported functions    |      01 - read coil \\ 05 - write single coil \\ 15 - write multiple coils | | Supported functions    |      01 - read coil \\ 05 - write single coil \\ 15 - write multiple coils |
  Relay output  Relay output
-Address range:         |                       200..207 +Nominal rating         |                       10A 250Vac (NO), 3A 250Vac (NC) 
-Relay mapping               coil 1(start address 00h) | +(resistive)               5A 30Vdc (NO), 3A 30Vdc (NC) | 
- +Radio 
-===== Terminals and wiring =====  +|Frequency band          |               ISM 868MHz (EU) | 
- +|Subband                 |  L 866.8MHz, 25mW, 1% utility 
-To power sensor ^ A RS485 bus  | +|Modulation               fSK 38.4kbps 80kHz bandwidth 
-:::            ^ B :::        +|Listen before talk         yes, delay limited to 20ms 
-:::            ^ C :::        +|Group address            32-bit, automatically generated 
-To power supply ^ L230V AC +|Connection time          10s power-on to network ready 
-:::             ^ N:::     +|Message delay            5ms from tx start to relay on | 
- +|Output power            |                           25mW | 
-{{ hiq_hardware:wm1_wiring.png?nolink&0x200  }} +|Operating range          3..300m with optical visibility|
- +
-<WRAP pagebreak></WRAP>+
  
-===== Serial configuration and timeout ===== +===== Modbus address setting ===== 
-  * Available baudrates 24009600, 19200, 38400 bps +Change is applied right awayno reset needed.
-  * Data bits and parity 8N1, 7E1, 8E1, 8N2 +
-  * :!: Max 64 bytes per transmition +
-  * Integrated 240 Ohm termination resistor+
  
-{{ hiq_hardware:wm1_serial.png?nolink&0x500  }}+{{ hiq_hardware:WR-1_address_settings.png?nolink&0x500  }}
  