Three phase power-sensor
Model number: | PM3-I-D |
---|---|
Connect to: | MC-230 |
RS485 power sensor bus A - B | |
Mounting: | DIN rail, 3M, 53 mm |
Dimensions: | 53 × 84 × 66 mm |
Used for measuring power and energy of | |
---|---|
✔ | three-phase energy sources |
✔ | three-phase energy consumers |
The PM-3-IQ is intended for energy measurements in three-phase electrical power network and can be used in residential, industrial and utility applications. Power-sensor measures energy directly in 4-wire networks according to the principle of fast sampling of voltage and current signals.
Connecting terminals can be sealed up against non-authorized access with protection covers. They are built to be fastened according to EN 60715 standard. Power-sensor has built-in RS485 serial communication with the MODBUS protocol which enables data transmission and thus connection of the measuring places into the network for the control and management with energy.
Nominal voltage | 3×230/400 VAC (-20..+15%) |
Power connector | 1,5 .. 16 mm2 |
Reference current | 5 A |
Maximum current | 65 A |
Operational frequency range | 50 or 60 Hz |
Internal power consumption | < 8 VA |
Communication type | RS485(half-duplex) |
Communication protocol | Modbus RTU |
Accuracy | |
---|---|
Active energy (Wh) | Class 1 IEC 62053-21 |
class B EN 50470-3 | |
±1.5% from Imin to Itr | |
±1% from Itr to Imax | |
Ambient conditions and Safety | |
Dust/water protection | IP50 |
Operating temp. range | -25 … 55°C |
Indoor sensor | yes |
Protection class | II |
EC Directives conformity | |
EC Directive on Measuring Instruments 2014/32/EU | |
EC Directive on EMC 2014/30/EU | |
EC Directive on Low Voltage 2014/35/EU | |
EC Directive WEEE 2002/96/EC |