12 temperature sensor inputs
IEX-2 temperature measurement module with 12 Pt1000 inputs
Model number: | AIR-12 |
---|---|
Mounting: | DIN rail, 3M |
Dimensions: | 53x117x58mm |
Compatible sensors: | |
---|---|
Pt1000 temperature probe | S-PT1000 |
Applications
- temperature measurements
Technical specification
Number of i/o points | 12 analog inputs |
Input type | software selectable (common for all inputs): |
- Pt100/1000 (DIN751), measuring range -100..300°C | |
- Ni100/1000 (DIN43760), measuring range -50..160°C | |
- Ni100/1000 (Landis & Gyr), measuring range -50..160°C | |
- potentiometer 0..2000 ohm | |
Connection type | 2-wire or 3-wire |
Wire resistance | 20 ohm max. (3-wire mode) |
A/D converter | V/f conversion with auto calibration |
Accuracy | 0.1% of measuring range |
Resolution | 14 bits (input modes with 0.1% accuracy) |
12 bits (input modes with 0.5%/1% accuracy) | |
Sensor current | 0.2mA (each sensor) |
Temperature drift | +/-0.01%/°C of measuring range |
Scan time | 30ms..1120ms, depends on input mode |
Integration time | 20ms or 60ms, depends on input mode |
Calibration reference | 150.00 ohm, 1500.0 ohm |
Accuracy, scan time | software selectable, depends on input mode |
Power supply | 24V (19..28V), 50mA |
Galvanic isolation | 1kV between digital and analog circuit no isolation between channels |
IEX-2 baud rate | 20, 50, 100, 250, 500kbps, auto selectable |
Operating conditions | 0..50°C, 0..85% rh non-condensing |
Mounting | DIN rail (35mm) |
Dimension | 53x117x58mm |
Weight gross | 160g |
Enclosure protection | IP20 |
Level of ambient pollution | 2 |
Standards | EN 61131-1, EN 61131-2, EN 50090-2-2 |