User Tools

Site Tools


en:hotel:hardware:hr-2-iq

This is an old revision of the document!


Hotel room controller

Hotel room master controller

Model number: HR-2
Mounting: DIN rail, 6M, 106mm
Dimensions: 106x108x58mm

Applications

  • Hotel room automation

Features

  • Welcome light
  • Power relay
  • HVAC control
  • Room SOS

General description

Hotel room controller controls all basic hotel room devices: welcome light, power relay, HVAC, card holder and SOS pull-switch. By itself is sufficient for basic hotel room automation. It is easy configurable and can be upgraded with many additional expansion units so it ensures practically any level of hotel room automation.

Easy commissioning with auto-addressing, easy configuration and advanced diagnostic ensures cost effective and quick system set-up and easy maintenance during whole life cycle.

Technical specification

Relay outputs: 3A/250V
Lock output: 500mA/12VDC
Transistor outputs: 250mA/24VDC
Communication: RS485, 2 × IEX bus
Power supply: 240V
Ingress protection: IP20
Operating temperature: 0..45°C
Storage temperature: -20..75°C
Relative humidity: 0..95% n/c

Terminals

Power supply 240 V AC L 1 Power supply input Digital inputs common 19 GND Common
N 2 Digital inputs 20 IX0 Card holder
Room power relay PWR 3 Relay outputs 21 IX1 Thermostat
Fan-coil 1st speed F1 4 22 IX2 Main door reed relay
Fan-coil 2nd speed F2 5 23 IX3 Welcome light push-button
Fan-coil 3rd speed F3 6 24 IX4 SOS pull-switch
Fan-coil valve VA 7 25 IX5 Info panel control push-button
Welcome light QX0 8 26 IX6 Window switch
Thermostat ECO mode QX1 9 27 IX7
Internal IEX bus GND GND 10 Internal IEX bus +12 VDC source 28 +12V Access control +12V
Internal IEX bus CANL ICANL 11 RS485 29 A Access control RXD-A
Internal IEX bus CANH ICANH 12 30 B Access control TXD-B
Internal IEX bus +24V +24V 13 GND 31 GND Access control GND
External IEX bus GND GND 14 External IEX bus GND 32 GND LOCK and Qx2-4 common
External IEX bus CANL ECANL 15 Lock output 33 LOCK Door lock
External IEX bus CANH ECANH 16 Transistor outputs 34 QX2 Info panel - Make My Room
External IEX bus in +24V +IN 17 35 QX3 Info panel - Do Not Disturb
External IEX bus out +24V +OUT 18 36 QX4 Info panel - Room Service Request
en/hotel/hardware/hr-2-iq.1542873841.txt.gz · Last modified: 2018/11/22 08:04 by goran.kocjancic