User Tools

Site Tools


en:goflex_hems:api

Application Programming Interface (API)

Direct loads control

load_set[i] bit R/W Managed load state; 0=off, 1=on; i = 10..17
analog_out[i] int R/W Analog output value in % i = 10..13

Timetable

timetable_cloud_once[i] bit RO Enabled cloud optimization for “once” actions; 0=disabled, 1=enabled; i=0..7
timetable_cloud_recurring[i] bit RO Enabled cloud optimization for “recurring” actions; 0=disabled, 1=enabled; i=0..7
timetable_analog_optimization[i] bit RO Enabled cloud optimization for analog timetable; 0=disabled, 1=enabled; i=0..3
optimization_index[i] int RW Timetable optimization index (0=broadcast = all timetables); i=0..50
optimization_start[i] int RW Timetable optimization start time; hhmmw; hh=hour, mm=minute, w=weekday(1=monday); i=0..50
optimization_time[i] int RW Timetable optimization period in min; i=0..50
optimization_command[i] int RW Timetable optimization command, auto set to 0 after being processed - see following table; i=0..50
optimization_value[i] int RW Timetable optimization value , depends of optimization_command - see following table; i=0..50

Variable optimization_command triggers timetable manipulation process so make sure to set all other variables before.

optimization_command optimization_value
1 managed load once actions 0 Set OFF
1 Set ON
-1 Delete
2 managed load recurring actions 0 Set OFF
1 Set ON
-1 Delete
3 tariff timetable 0 Set LO
1 Set HI
2 Set DYNAMIC
-1 Delete Dynamic
4 set mask 0..0xFF Set once on/off as per bit value
5 analog timetable 0..100 Set 0..100%
-1 Delete Analog
6 battery setpoint -100..0 Set discharge 0..100%
0..100 Set charge 0..100%
-31768 Set auto
en/goflex_hems/api.txt · Last modified: 2018/10/05 13:32 by goran.kocjancic