Commissioning
Control system
HEMS controller HC-IQ-HEMS and all communication interfaces are supplied with preinstalled firmware.
For system configuration use HIQ HEMS Configurator .
Power meters
- Connect only one new power meter at the time.
- In HIQ HEMS Configurator go to settings page. New power-meter should be detected (Address and Type should be displayed).
- Long-press button on power meter until -SET- is displayed.
- Press New address and enter new address according to following table.
Device | Address |
---|---|
Grid | 150 |
1st power plant | 154 |
2nd power plant | 155 |
3rd power plant | 156 |
1st storage | 157 |
2nd storage | 158 |
1st consumer | 160 |
2nd consumer | 161 |
… | … |
8th consumer | 167 |
Load managers
Add new device
- In HIQ HEMS Configurator go to wireless page
- Click on device which will be added
- Wait for network open - waiting device status.
- Press button on device.
- Wait until device is addressed and configured.
Procedure can be interrupted with “close network” button.
Remove device
- Reset device:
- power off wireless device for a few seconds.
- After powering on wait for a few seconds for device to boot on.
- Press and hold button, LED indicator will go off, then green and at the end red.
- Release button.
- In HIQ HEMS Configurator go to wireless page
- Reset device should have error state (yellow sign with exclamation)
- Click on reset device to clear place.
Control devices
- In HIQ HEMS Configurator go to wireless page
- Press icon for control device (wireless enocean push-button) to be configured
- On control device press 0 (off) button
- On control device press 1 (on) button
Sensors
Add new sensor
- Adjust sensor address with DIP-switches according following table
- In HIQ HEMS Configurator click on sensor which will be added
- Wait for network open - waiting device status
- Power on and pres button on sensor
- Wait until sensor is configured
Procedure can be interrupted with “close network” button.
Sensor | Address | DIP switch settings |
---|---|---|
S1 | 60 | |
S2 | 61 | |
S3 | 62 | |
S4 | 63 | |
S5 | 64 | |
S6 | 65 | |
S7 | 66 | |
S8 | 67 |
Remove sensor
- Reset sensor:
- Power off sensor for few seconds
- Reconnect sensor power supply
- After sensor power on (but within 20 sec) press and hold button for at least 6 sec
- In HIQ HEMS Configurator reset device should show error
- Click on error icon to free occupied space