Table of Contents
myHIQ Home
myHIQ is a custom application built for specific projects based on CybroMiniScada. It can be fully customized for end-user needs.
CyBroMiniScada variables
home controller address | c+home controller address | find on silver sticker on top of HC-HIQ |
---|
On/Off devices
All On/Off devices (lights, managed power sockets, exhaust fans, …) are controlled by LC-10-IQ device controller. myHIQ application displays device status and allows to toggle device output.
Device controller variables
HIQ-DC | id | output | description |
---|---|---|---|
LC-10-IQ | lc00..lc04 | qx00..qx09 | r/w; 0=off, 1=on |
Dimmers
Dimmable dvices (lights and some ceiling fans) are controlled by several device controllers, depending on controlled devices:
- LD-V4-IQ for LED stripes
- LD-P4-IQ for 230 V dimmable lights and ceiling fans
- LD-D8-IQ for DALI lights
myHIQ application displays the device's on / off status and output intensity, and allows to control both.
Device controller variables
HIQ-DC | id | output | description |
---|---|---|---|
LD-V4-IQ LD-P4-IQ LD-D8-IQ | ld00..ld04 | qx00..qx03 | r/w, 0=off, 1=on |
qw00..qw03 | r/w; 0..100 % |
Blinds
Blinds are controlled by a BC-5-IQ device controller.myHIQ application displays and sets the blind position.
Device controller variables
HIQ-DC | id | output | description |
---|---|---|---|
BC-5-IQ | bc00..bc01 | qxs00up..qxs04up | r/o; 0=off, 1=moving up |
qxs00dn..qxs04dn | r/o; 0=off, 1=moving down | ||
blinds_position_00..04 | r/o; 0..100 % | ||
blinds_setpoint_00..04 | r/w; 0..100 % , -1=stop |
Scenes
Scenes are implemented directly in HIQ-HC. There is no need to use scene controller for using scenes from myHIQ application.
Home controller variables
HIQ-HC variable | id | description |
---|---|---|
scene_status[0] | index=0..31 | r/o; 0=scene inactive, 1=scene active, 255=scene not defined |
global_scene_request | / | w/o; 0..31=set scene 0..31, -1=idle |
global_memory_request | / | w/o; 0..31=memorize scene 0..31, -1=idle |
Thermostats
Temperature regulation is done using TH-1M-IQ, TH-1T-IQ or TH-2-IQ thermostat and FC-1-IQ for fan-coils or HC-IQ for radiators.
Device controller variables
HIQ-HC | description | ||
---|---|---|---|
HC-IQ | hvac_mode | r/w; 0=off, 1=heating, 2=cooling | |
HIQ-DC | id | output | description |
TH-1M-HIQ TH-1T-IQ TH-2-IQ | th00..th04 | setpoint | r/w; *0.1 °C (234=23.4 °C) |
temperature | r/o; *0.1 °C (234=23.4 °C) | ||
humidity | r/o; % RH | ||
active | r/w; 0=inactive (uses idle setpoint), 1=active (use setpoint) | ||
FC-1-IQ | fc00..fc04 | valve | r/o; 0=off, 1=on |
fan_speed | r/o; 0..3 |