User Tools

Site Tools


en:hems:methods_resources:manufacture

This is an old revision of the document!


Manufacture

MC-230

Power-meters

Modbus settings for power-meters we supply: 9600 8n2; ID: 149

PM1-E-D

Factory setting: 2400 8n1; ID: 1

Put power-meter in set mode by pressing button until -SET- is displayed on power-meter display.

Parameter Address (hex) Format Default value (hex) New value (hex)
Parity / Stop bits 40019 (00 12) float 0 (00 00 00 00) = n1 3 (40 40 00 00) = n2
Meter ID 40021 (00 14) float 1 (3F 80 00 00) = 1 149 (43 15 00 00) = 149
Baud Rate 40029 (00 1C) float 0 (00 00 00 00) = 2400 2 (40 00 00 00) = 9600

CyBro-2-230-E configuring SW: eastron_config.zip

PM3-I-D

Power-meters are supplied according to our specifications - no configuration needed before sending.