1-ph current transformer
Split core current transformer 50A
Model number: | CT-1-E-50 |
---|---|
Connect to: | PM1-E-D-CT |
terminals 1 -2 | |
Mounting: | on wire |
Dimensions: | 41 × 24 × 27 mm |
- Split core
- Safe operation
- Mini in size
- Very easy mounting
- Wide inner window
General description
The CT1-E-50 split core current transformer is designed for fast and easy installation. The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken off line and disconnected for CT installation. This method permits a safer easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary circuit.
Technical specifications
Frequency | 50-60 Hz |
Rated current | 50 A |
Accuracy | ±1% from 20% to 120% of rated current |
Phase angle | less than 2 degrees at 50% of rated current |
Insulation voltage | 600 VAC |
Maximum primary voltage | 5000 VAC (insulated conductor) |
Dielectric strength | 2.5 kV/1mA/1min |
Operating temperature | -15 to 60°C |
Operating humidity | < 85 % |
Case material | PC/UL94-V0 |
Bobin | PBT |
Core | Permalloy |
Internal structure | Epoxy |
Leads | UL 1015, Twisted pair, 22 AWG |