en:hiq_hw:pm3-i-d
Table of Contents
Three phase power-sensor
Three phase power-sensor
Model number: | PM3-I-D |
---|---|
Connect to: | MC-230 |
RS485 power sensor bus A - B | |
Mounting: | DIN rail, 3M, 53 mm |
Dimensions: | 53 × 84 × 66 mm |
Used for measuring power and energy of | |
---|---|
✔ | three-phase energy sources |
✔ | three-phase energy consumers |
Applications
- Digital multi-function power-sensor for 3-phase sources or consumers
Features
- Three phase direct connection up to 65 A
- Serial RS485 communication
- Display LCD 7+1 digit
- Multi-functional front LED
General description
The PM-3-IQ is intended for energy measurements in three-phase electrical power network and can be used in residential, industrial and utility applications. Power-sensor measures energy directly in 4-wire networks according to the principle of fast sampling of voltage and current signals.
Connecting terminals can be sealed up against non-authorized access with protection covers. They are built to be fastened according to EN 60715 standard. Power-sensor has built-in RS485 serial communication with the MODBUS protocol which enables data transmission and thus connection of the measuring places into the network for the control and management with energy.
Technical specifications
Nominal voltage | 3×230/400 VAC (-20..+15%) |
Power connector | 1,5 .. 16 mm2 |
Reference current | 5 A |
Maximum current | 65 A |
Operational frequency range | 50 or 60 Hz |
Internal power consumption | < 8 VA |
Communication type | RS485(half-duplex) |
Communication protocol | Modbus RTU |
Accuracy | |
---|---|
Active energy (Wh) | Class 1 IEC 62053-21 |
class B EN 50470-3 | |
±1.5% from Imin to Itr | |
±1% from Itr to Imax | |
Ambient conditions and Safety | |
Dust/water protection | IP50 |
Operating temp. range | -25 … 55°C |
Indoor sensor | yes |
Protection class | II |
EC Directives conformity | |
EC Directive on Measuring Instruments 2014/32/EU | |
EC Directive on EMC 2014/30/EU | |
EC Directive on Low Voltage 2014/35/EU | |
EC Directive WEEE 2002/96/EC |
Connection
Manual
en/hiq_hw/pm3-i-d.txt · Last modified: 2019/07/24 08:16 by goran.kocjancic