Table of Contents
Blind thermostat
blind electronic thermostat
Model number: | TH-2-IQ |
---|---|
Mounting: | on-wall |
Dimensions: | 71×71×27mm |
Applications
- room / heating zone thermostat
Features
- alternate setpoint
- fan options:
- manual fan speed
- fan speed limits
- fan-max with time limitation
- sensor calibration
- various sensor options:
- internal
- external
- remote
- humidity meter
General description
TH-2-IQ module belongs to room/zone thermostat controllers. It can be used for any heating and/or cooling system including: fan-coils, hot water or electrical radiators, ceiling fans, floor/ceiling heating/cooling, split AC. TH series provide maximum comfort and energy saving functionality. Set-points are selectable through other devices.
Advanced functionality including smart-phone operation, internet operation, scheduling, HIQ automations, automatic weather response and more are provided when connected to HIQ Home Controller and HIQ universe.
Additional humidity measurement.
Technical specification
Temperature measurement: | internal or external |
Power supply: | 24V/10mA |
Ingress protection: | IP20 |
Operating temperature: | 0..45°C |
Storage temperature: | -20..75°C |
Temperature range: | 0..45°C |
Relative humidity: | 0..95% n/c |
Weight: | 50g |
Terminals
IEX2 BUS | +24V | IEX2 bus |
---|---|---|
CANH | ||
CANL | ||
GND | ||
External temperature sensor ES / ES-A | TS1 | Temperature sensor input |
GND |
When installing: “Autoaddress” button will link FC-1-IQ unit with lowest serial number with thermostat with lowest serial number and so on.