Wireless Modbus Relay
Wireless Modbus Relay
Model number: | WR-1 |
---|---|
Frequency: | ISM 868MHz (EU) |
Dimensions: | 93x45x27 mm |
Applications
- Remote controlled relay. Act as modbus RTU slave. Optimal for long range, no hopping.
Installation and mounting
Carefully open WR-1 module and configure serial communication with jumpers. (Default configuration is 9600bps, 8N1 with normal timeout)
Place WR-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.
- Connect RS485 terminals to WR-1 RS485 terminals
- A - A
- B - B
- C - GND
- Connect to 230V power supply
- Configure radio pairing
Features
- remote controlled relay
- act as modbus RTU slave
- very long range, no hopping
- up to 8 relays per network
- protected private connection
- multiple addressable groups
Technical specification
Power supply: | 230V, 50/60Hz, 1W |
Ingress protection: | IP20 |
Operating temperature: | -20..50°C |
Storage temperature: | -40..85°C |
Relative humidity: | 0..85% n/c |
Terminals and wiring
To power sensor | A | RS485 bus |
---|---|---|
B | ||
C | ||
To power supply | L | 230V AC |
N |
Serial configuration and timeout
- Available baudrates 2400, 9600, 19200, 38400 bps
- Data bits and parity 8N1, 7E1, 8E1, 8N2
Max 64 bytes per transmition
- Integrated 240 Ohm termination resistor
Radio pairing configuration
Create new secure group
* turn on all devices as the same time * within 10 seconds, while RF LED is blinking, press and hold button on one of the devices * after a second, the new address is randomly generated and sent to all devices. RF LED will blink 3 times to confirm the new address.
Add new device to the group
* turn on the device * within 10 seconds, press and hold button on one of the existing devices * after a second, the existing group address is sent to the new device. RF LED will blink 3 times to confirm the address is sent.
Examples
Connection check
- press the button shortly
With each press of the button, the relay will switch on/off. Other devices are not affected.
Factory reset
- Hold button and turn the device ON
- RF led will blink twice. Group address is now reset to default.
- Other devices will not be affected.