Wireless Modbus Relay

Wireless Modbus Relay

Model number: WR-1
Frequency: ISM 868MHz (EU)
Dimensions: 93x45x27 mm

Applications

  • Remote controlled relay. Act as modbus RTU slave. Optimal for long range, no hopping.

Installation and mounting

  • :!: Carefully open WR-1 module and configure serial communication with jumpers. (Default configuration is 9600bps, 8N1 with normal timeout)
  • :!: Place WR-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.
  • Connect RS485 terminals to WR-1 RS485 terminals
    • A - A
    • B - B
    • C - GND
  • Connect to 230V power supply
  • Configure radio pairing

Features

  • remote controlled relay
  • act as modbus RTU slave
  • very long range, no hopping
  • up to 8 relays per network
  • protected private connection
  • multiple addressable groups

Technical specification

Power supply: 230V, 50/60Hz, 1W
Ingress protection: IP20
Operating temperature: -20..50°C
Storage temperature: -40..85°C
Relative humidity: 0..85% n/c

Terminals and wiring

To power sensor A RS485 bus
B
C
To power supply L 230V AC
N

Serial configuration and timeout

  • Available baudrates 2400, 9600, 19200, 38400 bps
  • Data bits and parity 8N1, 7E1, 8E1, 8N2
  • :!: Max 64 bytes per transmition
  • Integrated 240 Ohm termination resistor

Radio pairing configuration

Create new secure group

* turn on all devices as the same time
* within 10 seconds, while RF LED is blinking, press and hold button on one of the devices
* after a second, the new address is randomly generated and sent to all devices. RF LED will blink 3 times to confirm the new address.

Add new device to the group

* turn on the device
* within 10 seconds, press and hold button on one of the existing devices
* after a second, the existing group address is sent to the new device. RF LED will blink 3 times to confirm the address is sent.

Examples

Connection check

  • press the button shortly

With each press of the button, the relay will switch on/off. Other devices are not affected.

Factory reset

  • Hold button and turn the device ON
  • RF led will blink twice. Group address is now reset to default.
  • Other devices will not be affected.